Low-Voltage Cabinet himna hlat zawng sawifiahna

Jul 16, 2025

Message pakhat dah la .

I. Low-Voltage Cabinet-te tana Core Safety Distance Specifications
Low-voltage cabinet-te himna hlat zawng specification hi a bul berah chuan ram pum standard "GB/T 7251.1-2017 Low-Voltage Switchgear leh Controlgear Assemblies" leh "GB 50054-2011 Low-Voltage Power Distribution Design Specifications" te a ni. Numerical mamawh bikte chu hetiang hi a ni:

1. Hma lam hnathawhna hlat zawng: A tlem berah 800mm (fixed cabinet) emaw 1000mm (drawer-type cabinet), maintenance personnel-te tan squatting emaw ding emaw huna hmanna tur hmun remchang siamsak (GB 50054, Section 4.2.5 atanga tarlan).

2. Rear maintenance distance: A tlem berah 600mm, a nih loh leh hnunglam kawngkhar luh a ngai a nih chuan 800mm tal.

3. Lateral aisle zau zawng: Double-row arrangement atan chuan cabinet inkar hlat zawng chu 1000mm tal a ni tur a ni; wall-a single-row arrangement atan chuan a sir lamah 200mm tal clearance dah tur a ni.

Thu belhchian dawl zawk:

- 800mm front clearance hi puitling arm span average (700mm vel) atanga chhut a ni a, tool handling atan allowance a awm bawk.

- Drawer-type cabinet te hian clearance dang an mamawh a, a chhan chu drawer te hi a kim vek tur a ni.

 

II. Low-Voltage Cabinet aia sang Safety Clearances neih theihna tura thil tul bik
Low-voltage cabinet chunga safety clearance hi ngaihthah a ni fo a, mahse heat dissipation leh high-voltage isolation atan hlauhawmna a awm a ni:

1. Top Clearance neih theihna tur:

- Standard low-voltage cabinets: 300mm aia tam emaw, a tlukpui emaw (heat dissipation mamawh);

- Cabinet chungah high-voltage busbar a awm chuan: 1200mm aia lian emaw, a tlukpui emaw (GB 50054 Section 4.3.3 atanga tarlan).

2. Cabinet Across-a Cable Tray Installation: Cabinet roof-ah cable tray dah a nih chuan, heat conduction-in equipment hnathawh a nghawng loh nan cable tray leh cabinet roof inkar hlat zawng chu 150mm aia tam emaw, a tlukpui emaw a ni tur a ni.